PAqua 1000D-2 Fresh Water Purification System

PAqua 1000D-2 is designed to purify drinking water to WHO guidelines from fresh water sources such as Rivers, Ponds, Lakes, biologically contaminated Municipal Supply and Boreholes.

The PAqua 1000D-2 is automatic in operation, easy to set up & use (4 hoses connected and single on/off button operation) with remote monitoring of system telemetry transmission back to base to aid optimal operation.

Ideal for small camps or temporary drinking water solutions while main water supplies are down in disaster, humanitarian or crisis zones.

  • Environmentally friendly with no corrosive or harmful chemicals needed
  • Lowest possible power consumpion utilising latest IE5 pump technology
  • Produces up to 1000ltr / hr of potable water supporting 3000 people / day
  • Simple to operate and fully autonomous including self-cleaning
  • Online remote monitoring and control
  • Disinfection produced “On Demand” killing Viruses, Pathogens & Bacteria
  • Sterilises storage containers holding potable water & extends its shelf life

Technical Data
Power & Pressure
240v AC 60 Hz 32A
Filtration Grundfos CME 1-3,upto 1,200ltrs/hr @ 2 BAR Pressure, 2 X DDA dosing pumps up to60ltrs/hr dosing of PAQUA disinfection each
Backwash Grundfos CME 1-3, up to 2,400ltrs/hr @2.2Bar pressure
Disinfection Grundfos CRNE 1S-5 100ltrs/hr @ 2 Bar pressure
Envirolyte ELA 900 Disinfection unit producing 72Ltres/hr Hypochlorous acid (PAQUA) up to 500ppm Free Available Chlorine (FAC)
Remote monitoring hub and modem over 3G/4G phone network or Cat5 direct internet cable DID controller with FAC probe up to 20ppm and ORP -2000 to 2000 mV continuous monitoring

Power Consumption: Average 2A / 500W.
Power Consumption: With Generator operating up to 10A 2.4KW Max.
Grundfos CME 1-3 & CRNE 1S-5 are IE5 efficiency rated

Ultra Filtration Membranes
2 Inge Dizzer 4040-4.0 1.5 capable of processing up to 1,200 ltrs/hr dependent of source water

Water Softener
Wrekin DX500 Mini twin cylinder: Max flow rate 600ltrs/hr, 24hrs/day

PAQUA
Anolyte can destroy mycobacterium, fungi, viruses, bacterial endospores, gram-positive/negative bacteria, including all pathogens currently considered high risk (i.e. MRSA, Clostridium difficile, Escherichia coli, norovirus, H5N1 avian flu, H1N1 swine flu, HIV, polio virus and Legionella).
PAQUA Can achieve (and exceed) 5 log10 reduction requirement within 10 seconds.

Actual Operation Data
Production Potable water per hour: max 1,000 litres max
Production volume Potable Water over 24hr period max 24,000ltrs
Temperature range 1-40°C

Potable water produced when ORP >650mV & FAC <2ppm via continuous on-board monitoring.

Dimensions, Supplied components
Overall size: Width: 1.5m Depth: 1m Height: 2m
Weight Dry: 480kg
Weight Wet: 700kg
Supply pipe length: 8m X 1”
Discharge / Drain pipe: 8m X 1 ½”
Potable water hose: 10m X ¾”
Non Potable water hose: 10m X ½”

Ingress Protection Rating: IP65